| 线规格号(钢比%) | 最高允许温度为下值时的载流量A | |
|---|---|---|
| +70°C | +80°C | |
| 16 (17%) | 79 | 111 |
| 25 (17%) | 109 | 147 |
| 40 (17%) | 152 | 198 |
| 63 (17%) | 211 | 265 |
| 100 (17%) | 293 | 355 |
| 125 (6%) | 338 | 405 |
| 125 (16%) | 345 | 410 |
| 160 (6%) | 403 | 473 |
| 160 (16%) | 411 | 480 |
| 200 (6%) | 473 | 546 |
| 200 (16%) | 483 | 553 |
| 250 (10%) | 561 | 634 |
| 250 (16%) | 568 | 639 |
| 315 (7%) | 658 | 732 |
| 315 (16%) | 670 | 741 |
| 400 (7%) | 781 | 854 |
| 400 (13%) | 789 | 859 |
| 450 (7%) | 846 | 917 |
| 450 (13%) | 855 | 923 |
| 500 (7%) | 913 | 981 |
| 500 (13%) | 923 | 989 |
| 560 (7%) | 990 | 1055 |
| 560 (13%) | 1002 | 1064 |
| 630 (7%) | 1078 | 1139 |
| 630 (13%) | 1090 | 1147 |
| 710 (7%) | 1175 | 1231 |
| 710 (13%) | 1188 | 1240 |
| 800 (4%) | 1273 | 1324 |
| 800 (8%) | 1282 | 1330 |
| 800 (13%) | 1294 | 1338 |
| 900 (4%) | 1386 | 1429 |
| 900 (8%) | 1395 | 1434 |
| 1000 (4%) | 1496 | 1530 |
| 1120 (4%) | 1622 | 1646 |
| 1120 (8%) | 1635 | 1654 |
| 1250 (4%) | 1756 | 1767 |
| 1250 (8%) | 1767 | 1773 |
| 注1: 最高允许温度+70℃的载流量, 系按基准环境温度为+25℃、无日照、无风、导线表面黑度为0.9条件计算的。 注2: 最高允许温度+80℃的载流量, 系按基准环境温度+25℃、日照0.1W/cm²、风速0.5m/s、海拔1000m、导线表面黑度为0.9条件计算的。 注3: JL/G1A、JL/G1B、JL/G2A、JL/G2B、JL/G3A型铝合金绞线性能见GB/T 1179—1999附表D4。 | ||
| 导线规格号(钢比%) | 最高允许温度为下值时的载流量A | |
|---|---|---|
| +70°C | +80°C | |
| 16 (17%) | 81 | 112 |
| 25 (17%) | 112 | 149 |
| 40 (17%) | 156 | 201 |
| 63 (17%) | 217 | 269 |
| 100 (6%) | 296 | 356 |
| 125 (6%) | 347 | 411 |
| 125 (16%) | 354 | 416 |
| 160 (6%) | 414 | 481 |
| 160 (16%) | 423 | 487 |
| 200 (6%) | 485 | 554 |
| 200 (16%) | 497 | 563 |
| 250 (10%) | 576 | 644 |
| 250 (16%) | 583 | 649 |
| 315 (7%) | 675 | 744 |
| 315 (16%) | 688 | 753 |
| 400 (7%) | 800 | 864 |
| 400 (13%) | 809 | 871 |
| 450 (7%) | 869 | 932 |
| 450 (13%) | 880 | 939 |
| 500 (7%) | 938 | 998 |
| 500 (13%) | 950 | 1005 |
| 560 (7%) | 1018 | 1073 |
| 560 (13%) | 1030 | 1081 |
| 630 (4%) | 1101 | 1153 |
| 630 (13%) | 1120 | 1166 |
| 710 (4%) | 1201 | 1246 |
| 710 (13%) | 1221 | 1260 |
| 800 (4%) | 1310 | 1347 |
| 800 (8%) | 1318 | 1352 |
| 900 (4%) | 1424 | 1453 |
| 900 (8%) | 1434 | 1458 |
| 1000 (8%) | 1548 | 1563 |
| 1120 (8%) | 1680 | 1682 |
| 注1: 最高允许温度+70℃的载流量, 系按基准环境温度为+25℃、无日照、无风、导线表面黑度为0.9条件计算的。 注2: 最高允许温度+80℃的载流量, 系按基准环境温度+25℃、日照0.1W/cm²、风速0.5m/s、海拔1000m、导线表面黑度为0.9条件计算的。 注3: JLHA2/G1A、JLHA2/G1B、JLHA2/G3A (JLHA1/G1A、JLHA1/G1B、JLHA1/G3A) JLHA2型钢芯铝合金绞线性能见GB/T1179-1999附表D5、附表D6。 a JLHA2/G1A、JLHA2/G1B、JLHA2/G3A型钢芯铝合金绞线单线截面、额定拉断力比JLHA1/G1A、JLHA1/G1B、JLHA1/G3A略大, 个别规格导线载流量也略大, 但均在5A以内。 | ||