id
stringlengths
12
16
title
stringlengths
6
140
description
stringlengths
76
139k
cpes
listlengths
0
0
cvss_v4_0
null
cvss_v3_1
float64
2.5
10
cvss_v3_0
float64
1.9
10
cvss_v2_0
null
ICSA-22-335-02
Horner Automation Remote Compact Controller
The Config-files of Horner Automation 's RCC 972 with firmware version 15.40 are encrypted with weak XOR encryption vulnerable to reverse engineering. This could allow an attacker to obtain credentials to run services such as File Transfer Protocol (FTP) and Hypertext Transfer Protocol (HTTP).CVE-2022-2640 has been ass...
[]
null
null
7.5
null
ICSA-18-051-01
ABB netCADOPS Web Application
A vulnerability exists in the password entry section of netCADOPS Web Application that may expose critical database information. CVE-2018-5477 has been assigned to this vulnerability. A CVSS v3 base score of 5.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:N).
[]
null
null
5.8
null
ICSA-19-232-01
Zebra Industrial Printers
Zebra printers are shipped with unrestricted end-user access to front panel options. If the option to use a passcode to limit the functionality of the front panel is applied, specially crafted packets could be sent over the same network to a port on the printer and the printer will respond with an array of information ...
[]
null
null
5.3
null
ICSA-21-285-01
Advantech WebAccess SCADA
An authenticated user can use API functions to disclose project names and paths from other users.CVE-2021-38431 has been assigned to this vulnerability. A CVSS v3 base score of 4.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:N/A:N).
[]
null
null
4.3
null
ICSA-20-280-01
Rockwell Automation ISaGRAF5 Runtime (Update A)
Some commands used by the ISaGRAF eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application 's directory, which could lead to rem...
[]
null
null
5.3
null
ICSA-23-299-06
Rockwell Automation FactoryTalk Services Platform
Due to inadequate code logic, a previously unauthenticated threat actor could potentially obtain a local Windows OS user token through the FactoryTalk Services Platform web service and then use the token to log in into FactoryTalk Services Platform. This vulnerability can only be exploited if the authorized user did no...
[]
null
8.1
null
null
ICSA-21-103-12
Siemens Tecnomatix RobotExpert
Affected applications lack proper validation of user-supplied data when parsing CELL files. This could result in an out of bounds write past the end of an allocated structure. An attacker could leverage this vulnerability to execute code in the context of the current process. (ZDI-CAN-12608)
[]
null
7.8
null
null
ICSA-22-053-02
GE Proficy CIMPLICITY-Cleartext
CVE-2022-21798 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:A/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H).
[]
null
null
7.5
null
ICSA-24-275-01
Optigo Networks ONS-S8 - Spectra Aggregation Switch
The web service for ONS-S8 - Spectra Aggregation Switch includes functions which do not properly validate user input, allowing an attacker to traverse directories, bypass authentication, and execute remote code. The web server for ONS-S8 - Spectra Aggregation Switch includes an incomplete authentication process, which ...
[]
null
9.1
null
null
ICSA-24-011-10
Siemens SIMATIC
In default installations of maxView Storage Manager where Redfish® server is configured for remote system management, a vulnerability has been identified that can provide unauthorized access.
[]
null
10
null
null
ICSA-21-257-08
Siemens Teamcenter
The "surrogate" functionality on the user profile of the application does not perform sufficient access control that could lead to an account takeover. Any profile on the application can perform this attack and access any other user assigned tasks via the "inbox/surrogate tasks". The affected application contains Insec...
[]
null
5.3
null
null
ICSA-23-264-01
Real Time Automation 460 Series
Real Time Automation 460 Series products with versions prior to v8.9.8 are vulnerable to cross-site scripting, which could allow an attacker to run any JavaScript reference from the URL string. If this were to occur, the gateway's HTTP interface would redirect to the main page, which is index.htm.
[]
null
null
9.4
null
ICSA-18-305-01
AVEVA InduSoft Web Studio and InTouch Edge HMI (formerly InTouch Machine Edition)
A remote attacker could send a carefully crafted packet to exploit a stack-based buffer overflow vulnerability during tag, alarm, or event related actions such as read and write, with potential for code to be executed. If InduSoft Web Studio remote communication security was not enabled, or a password was left blank, a...
[]
null
null
9.8
null
ICSA-22-069-07
Siemens Climatix POL909
The Group Management page of affected devices is vulnerable to cross-site scripting (XSS). The vulnerability allows an attacker to send malicious JavaScript code which could result in hijacking of the user's cookie/session tokens, redirecting the user to a malicious webpage and performing unintended browser action. The...
[]
null
4.3
null
null
ICSA-20-133-02
OSIsoft PI System (Update A)
A local attacker can modify a search path and plant a binary to exploit the affected PI System software to take control of the local computer at Windows system privilege level, resulting in unauthorized information disclosure, deletion, or modification.CVE-2020-10610 has been assigned to this vulnerability. A CVSS v3 b...
[]
null
null
5.1
null
ICSA-21-201-01
Mitsubishi Electric MELSEC-F Series
Malicious attacker may cause a denial-of-service condition in communication with the product by sending specially crafted packets.CVE-2021-20596 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H).
[]
null
null
7.5
null
ICSA-21-070-01
Schneider Electric IGSS SCADA Software
This vulnerability could result in loss of data or remote code execution when a malicious CGF (configuration group file) file is imported into an IGSS Definition.CVE-2021-22709 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:...
[]
null
null
7.8
null
ICSA-22-167-02
AutomationDirect DirectLOGIC with Serial Communication
The product is vulnerable to a specifically crafted serial message to the CPU serial port that will cause the PLC to respond with the PLC password in cleartext. This could allow an attacker to access and make unauthorized changes.CVE-2022-2003 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has bee...
[]
null
null
7.7
null
ICSA-22-102-01
Valmet DNA
An unauthenticated network user can craft specific packets targeting a Valmet DNA service, listening by default on a specific TCP port. By exploiting a predictable encryption key, the attacker can remotely trigger commands to be executed with system privileges.CVE-2021-26726 has been assigned to this vulnerability. A C...
[]
null
null
8.8
null
ICSA-18-114-03
Advantech WebAccess HMI Designer
Heap-based buffer overflow vulnerabilities caused by processing specially crafted .pm3 files may allow remote code execution.CVE-2018-8833 has been assigned to this vulnerability. A CVSS v3 base score of 6.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:L/I:L/A:L). Double free vulnerabilitie...
[]
null
null
6.3
null
ICSA-22-354-03
ARC Informatique PcVue
A cleartext storage of sensitive information vulnerability exists in PcVue versions 8.10 through 15.2.3. This could allow an unauthorized user to access the email and short messaging service (SMS) accounts configuration files to discover the associated simple mail transfer protocol (SMTP) account credentials and the SI...
[]
null
4.7
null
null
ICSA-23-215-01
Mitsubishi Electric GOT2000 and GOT SIMPLE
A denial-of-service and spoofing (session hijacking of data connections) vulnerability exists in the FTP server function on GOT2000 series and GOT SIMPLE series because the port number of a data connection can be easily guessed due to predictable exact value from previous values.
[]
null
null
5.9
null
ICSA-21-145-02
Rockwell Automation Micro800 and MicroLogix 1400
When an authenticated password change request takes place, this vulnerability could allow the attacker to intercept the message that includes the legitimate, new password hash and replace it with an illegitimate hash. The user would no longer be able to authenticate to the controller causing a denial-of-service conditi...
[]
null
null
6.1
null
ICSA-19-043-05
Siemens Intel Active Management Technology of SIMATIC IPCs
Bleichenbacher-style side channel vulnerability in TLS implementation in Intel Active Management Technology before 12.0.5 may allow an unauthenticated user to potentially obtain the TLS session key via the network. The security vulnerability could be exploited by an attacker with network access to the affected systems....
[]
null
5.3
null
null
ICSA-24-235-03
Authenticated Remote Code Execution affects Mobotix P3 and Mx6 cameras
The tcpdump feature does not properly validate input, which allows authenticated users to execute code.
[]
null
8.8
null
null
ICSA-17-299-02
Rockwell Automation Stratix 5100 (Update A)
Key reinstallation attacks (KRACK) work against the four-way handshake of the WPA2 protocol. KRACK takes advantage of the retransmission of a handshake message to prompt the installation of the same encryption key every time it receives message 3 from the access point. Retransmission of the handshake message from the a...
[]
null
null
6.9
null
ICSMA-21-187-01
Philips Vue PACS (Update B)
The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly. CVE-2020-1938 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L...
[]
null
null
2.7
null
ICSA-22-146-02
Horner Automation Cscape Csfont
The affected product is vulnerable to an out-of-bounds write, which may allow an attacker to execute arbitrary code.CVE-2022-27184 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The affected product is vulnerable...
[]
null
null
7.8
null
ICSA-17-129-01
Siemens devices using the PROFINET Discovery and Configuration Protocol (Update K)
Specially crafted PROFINET DCP broadcast packets sent to the affected products on alocal Ethernet segment (Layer 2) could cause a Denial-of-Service condition of someservices. The services require manual restart to recover.
[]
null
null
6.5
null
ICSA-18-107-04
Rockwell Automation Stratix and ArmorStratix Switches
A vulnerability in the Smart Install feature of Cisco IOS Software and Cisco IOS XE Software could allow an unauthenticated remote attacker to trigger a reload of an affected device, resulting in a denial of service (DoS) condition, or to execute arbitrary code on an affected device. The vulnerability is due to imprope...
[]
null
null
8.8
null
ICSA-23-299-05
Rockwell Automation FactoryTalk View Site Edition
FactoryTalk View Site Edition V11.0 insufficiently validates user input, which could potentially allow threat actors to send malicious data bringing the product offline. If exploited, the product would become unavailable and require a restart to recover resulting in a denial-of-service condition.
[]
null
7.5
null
null
ICSA-19-136-02
Fuji Electric Alpha7 PC Loader
An out-of-bounds read vulnerability has been identified, which may crash the system.CVE-2019-10975 has been assigned to this vulnerability. A CVSS v3 base score of 3.3 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:N/I:N/A:L).
[]
null
null
3.3
null
ICSA-21-105-01
Schneider Electric C-Bus Toolkit
The affected product is vulnerable to Improper Privilege Management, which could allow remote code execution when an unprivileged user modifies a file.CVE-2021-22716 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H). T...
[]
null
null
6.5
null
ICSA-23-236-04
CODESYS Development System
A missing brute-force protection in CODESYS Development System prior to 3.5.19.20 could allows a local attacker to have unlimited attempts of guessing the password within an import dialog.
[]
null
null
3.3
null
ICSA-22-046-01
Schneider Electric IGSS
A vulnerability exists that could cause heap-based buffer overflow, leading to denial of service and potentially remote code execution when an attacker sends multiple specially crafted messages.CVE-2022-24310 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector strin...
[]
null
null
5.3
null
ICSA-17-045-03
Siemens SIMATIC Authentication Bypass (Update D)
An attacker with knowledge of a valid user name, and physical or network access to the affected system could bypass the application-level authentication.
[]
null
null
9
null
ICSA-23-285-03
Siemens SICAM A8000 Devices
The web server of affected devices fails to properly sanitize user input for the /sicweb-ajax/tmproot/ endpoint. This could allow an authenticated remote attacker to traverse directories on the system and download arbitrary files. By exploring active session IDs, the vulnerability could potentially be leveraged to e...
[]
null
7.5
null
null
ICSA-23-166-11
Siemens SIMATIC S7-1500 TM MFP Linux Kernel
A memory overflow vulnerability was found in the Linux kernel’s ipc functionality of the memcg subsystem, in the way a user calls the semget function multiple times, creating semaphores. This flaw allows a local user to starve the resources, causing a denial of service. The highest threat from this vulnerability is to ...
[]
null
7.1
null
null
ICSMA-17-318-01
Philips IntelliSpace Cardiovascular System and Xcelera System Vulnerability
Credentials are stored in cleartext in system files that may allow an attacker with elevated privileges to gain unauthorized access to data to include patient health information, system resources, and misuse of connected assets. CVE-2017-14111 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has bee...
[]
null
null
7.2
null
ICSA-23-103-05
Siemens SCALANCE X-200IRT Devices
The SSH server on affected devices is configured to offer weak ciphers by default. This could allow an unauthorized attacker in a man-in-the-middle position to read and modify any data passed over the connection between legitimate clients and the affected device.
[]
null
6.7
null
null
ICSA-20-196-07
Siemens Opcenter Execution Core (Update B)
An authenticated user with the ability to create containers, packages or register defects could perform stored Cross-Site Scripting (XSS) attacks within the vulnerable software. The impact of this attack could result in the session cookies of legitimate users being stolen. Should the attacker gain access to these cooki...
[]
null
5.5
null
null
ICSA-22-088-04
Modbus Tools Modbus Slave
The affected product is vulnerable to a stack-based buffer overflow in the registration field. This may cause the program to crash when a long character string is used.CVE-2022-1068 has been assigned to this vulnerability. A CVSS v3 base score of 5.5 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U...
[]
null
null
5.5
null
ICSA-22-242-02
Hitachi Energy Gateway Station (GWS) Product
Hitachi Energy is aware of publicly disclosed reports of multiple vulnerabilities in open-source software components (OpenSSL and Node.JS) used in the Gateway Station (GWS) product. Versions are available to remediate the identified vulnerabilities.CVE-2020-1968, CVE-2020-8172, CVE-2020-8174, CVE-2020-8201, CVE-2020-82...
[]
null
null
8.1
null
ICSA-21-159-09
Siemens Solid Edge
The ugeom2d.dll library lacks proper validation of user-supplied data when parsing DFT files. This could result in an out of bounds write past the end of an allocated structure. An attacker could leverage this vulnerability to execute code in the context of the current process. (ZDI-CAN-12993) The jutil.dll library lac...
[]
null
7.8
null
null
ICSA-21-119-01
Texas Instruments SimpleLink
An integer overflow exists in the APIs of the host MCU while trying to connect to a WIFI network may lead to issues such as a denial-of-service condition or code execution.CVE-2021-22677 has been assigned to this vulnerability. A CVSS v3 base score of 8.4 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/U...
[]
null
null
9.8
null
ICSA-17-220-02
Moxa SoftNVR-IA Live Viewer
An uncontrolled search path element (DLL Hijacking) vulnerability has been identified.To exploit this vulnerability, an attacker could rename a malicious DLL to meet the criteria of the application, and the application would not verify that the DLL is correct. The attacker needs to have administrative access to the def...
[]
null
null
7.2
null
ICSA-19-318-05
ABB Power Generation Information Manager (PGIM) and Plant Connect
The affected product is vulnerable to authentication bypass, which may allow an attacker to remotely bypass authentication and extract credentials from the affected device.CVE-2019-18250 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:...
[]
null
null
9.8
null
ICSA-22-090-04
Mitsubishi Electric FA Products
This vulnerability allows a remote unauthenticated attacker to log in to the product by replaying an eavesdropped password hash. CVE-2022-25155 has been assigned to this vulnerability. A CVSS v3 base score of 5.9 has been assigned; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N). This vulnerability coul...
[]
null
null
6.8
null
ICSA-21-194-12
Siemens VxWorks-based Industrial Products (Update C)
There is a DHCP vulnerability in Wind River VxWorks, for versions prior to 6.5. This vulnerability could cause a heap overflow if exploited. CVE-2021-29998 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
[]
null
null
5.9
null
ICSA-17-292-01
SpiderControl MicroBrowser
An uncontrolled search path element vulnerability has been identified which could be exploited by placing a specially crafted DLL file in the search path. If the malicious DLL is loaded prior to the valid DLL, an attacker could execute arbitrary code on the system.CVE-2017-14010 has been assigned to this vulnerability....
[]
null
null
8.8
null
ICSA-17-243-04
OPW Fuel Management Systems SiteSentinel Integra and SiteSentinel iSite
An attacker may create an application user account to gain administrative privileges.CVE-2017-12733 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H). The application is vulnerable to injection of malicious SQL queri...
[]
null
null
8.2
null
ICSMA-19-311-02
Medtronic Valleylab FT10 and FX8
The affected products use multiple sets of hard-coded credentials. If discovered, they can be used to read files on the device.CVE-2019-13543 has been assigned to this vulnerability. A CVSS v3 base score of 5.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:N). The affected products u...
[]
null
null
9.8
null
ICSA-24-074-09
Siemens Sinteso EN Cerberus PRO EN Fire Protection Systems
The network communication library in affected systems does not validate the length of certain X.509 certificate attributes which might result in a stack-based buffer overflow. This could allow an unauthenticated remote attacker to execute code on the underlying operating system with root privileges. Successful exploit...
[]
null
5.9
null
null
ICSA-20-014-03
Siemens SCALANCE X Switches (Update B)
Affected devices contain a vulnerability that allows an unauthenticated attacker to violate access-control rules. The vulnerability can be triggered by sending GET request to specific uniform resource locator on the web configuration interface of the device. The security vulnerability could be exploited by an at...
[]
null
8.8
null
null
ICSA-19-274-02
Yokogawa Products
Service paths in some Yokogawa applications are unquoted and contain spaces. This may allow a local attacker to execute malicious files by the service privilege.CVE-2019-6008 has been assigned to this vulnerability. A CVSS v3 base score of 8.4 has been calculated; the CVSS vector string is (AV:L/AC:L/PR:N/UI:N/S:U/C:H/...
[]
null
null
8.4
null
ICSA-18-114-01
Vecna VGo Robot (Update A)
An attacker may be able to capture firmware updates through the adjacent network.CVE-2018-8860 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N). User accounts may be able to execute commands that are outside the sco...
[]
null
null
4.7
null
ICSA-18-242-01
Philips e-Alert Unit
The software does not validate input properly, allowing an attacker to craft the input in a form that is not expected by the rest of the application. This would lead to parts of the unit receiving unintended input, which may result in altered control flow, arbitrary control of a resource, or arbitrary code execution.CV...
[]
null
null
7.5
null
ICSA-24-011-06
Siemens Teamcenter Visualization and JT2Go
The affected applications contain an out of bounds read past the end of an allocated structure while parsing specially crafted CGM files. This could allow an attacker to execute code in the context of the current process. The affected applications contain a null pointer dereference vulnerability while parsing specially...
[]
null
7.8
null
null
ICSA-23-131-01
Siemens Solid Edge
STEPTools v18SP1 ifcmesh library (v18.1) is affected due to a null pointer dereference, which could allow an attacker to deny application usage when reading a specially constructed file, resulting in an application crash. (ZDI-CAN-19429) Affected applications contain an out of bounds read past the end of an allocated b...
[]
null
7.8
null
null
ICSA-21-222-01
Siemens JT2Go and Teamcenter Visualization products
An out-of-bounds write issue exists in the DXF file-recovering procedure in the Open Design Alliance Drawings SDK (All versions prior to 2022.4) resulting from the lack of proper validation of user-supplied data. This can result in a write past the end of an allocated buffer and allow attackers to cause a denial-of-ser...
[]
null
5.5
null
null
ICSA-19-346-02
Omron PLC CJ and CS Series
An attacker could spoof arbitrary messages or execute commands. CVE-2019-18259 has been assigned to this vulnerability. A CVSS v3 base score of 5.6 has been calculated; the CVSS vector string is (AV:N/AC:H/PR:N/UI:N/S:U/C:L/I:L/A:L).). An attacker could monitor traffic between the PLC and the controller and replay requ...
[]
null
null
8.6
null
ICSA-20-315-03
Schneider Electric PLC Simulator for EcoStruxure Control Expert
A vulnerability exists that could cause a crash of the PLC simulator present in EcoStruxure Control Expert software when receiving a specially crafted request over Modbus.CVE-2020-7538 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:...
[]
null
null
7.5
null
ICSA-22-109-03
FANUC ROBOGUIDE Simulation Platform
The affected product is vulnerable to misconfigured binaries, allowing users on the target PC with SYSTEM level privileges access to overwrite the binary and modify files to gain privilege escalation.CVE-2021-38483 has been assigned to this vulnerability. A CVSS v3 base score of 6.0 has been calculated; the CVSS vector...
[]
null
null
6.1
null
ICSA-20-224-02
Schneider Electric APC Easy UPS On-Line
A vulnerability exists when accessing a vulnerable method of `FileUploadServlet` that may lead to uploading executable files to non-specified directories.CVE-2020-7521 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H...
[]
null
null
9.8
null
ICSA-21-257-02
Johnson Controls Sensormatic Electronics KT-1
The KT-1 door controller is susceptible to replay attacks.CVE-2021-27662 has been assigned to this vulnerability. A CVSS v3 base score of 8.6 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:L/A:L).
[]
null
null
8.6
null
ICSA-21-040-08
Siemens SIMARIS Configuration (Update A)
During installation to default target folder, incorrect permissions are configured for the application folder and subfolders, which may allow an attacker to gain persistence or potentially escalate privileges if a user with elevated credentials logs onto the machine.CVE-2020-28392 has been assigned to this vulnerabilit...
[]
null
null
4.4
null
ICSA-22-090-06
General Electric Renewable Energy MDS Radios
This previously disclosed vulnerability in the GoAhead Webserver may allow remote code execution in iNET/iNET II, TD220X, and TD220MAX series radios.CVE-2017-17562 has been assigned to this vulnerability. A CVSS v3 base score of 10.0 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H). ...
[]
null
null
8.4
null
ICSA-21-313-05
OSIsoft PI Vision
A remote attacker with write access to PI Vision could inject code into a display. Unauthorized information disclosure, modification, or deletion is possible if a victim views or interacts with the infected display using Microsoft Internet Explorer. The impact affects PI System data and other data accessible with victi...
[]
null
null
3.1
null
ICSA-21-131-04
Siemens SINAMICS Medium Voltage Products Remote Access (Update B)
UltraVNC revision 1198 contains multiple memory leaks in VNC client code, which could allow an attacker to read stack memory and can be abused for information disclosure. Combined with another vulnerability, it can be used to leak stack memory and bypass ASLR. This vulnerability appears to be exploitable via network co...
[]
null
7.5
null
null
ICSA-21-133-04
OPC UA Products Built with the .NET Framework 4.5, 4.0, and 3.5
The OPC UA .NET Framework can expose sensitive information to an actor who is not authorized to have access.CVE-2021-27434 has been assigned to this vulnerability. A CVSS v3 base score of 7.2 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:L/I:N/A:L).
[]
null
null
7.2
null
ICSA-21-224-02
Horner Automation Cscape
The affected application lacks proper validation of user-supplied data when parsing project files. This could lead to an out-of-bounds write. An attacker could leverage this vulnerability to execute code in the context of the current process.CVE-2021-32995 has been assigned to this vulnerability. A CVSS v3 base score o...
[]
null
null
7.8
null
ICSA-21-007-04
Delta Electronics CNCSoft-B
The affected product is vulnerable to an out-of-bounds write while processing project files, which may allow an attacker to execute arbitrary code.CVE-2020-27287 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H). The a...
[]
null
null
7.8
null
ICSA-23-285-13
Mitsubishi Electric MELSEC-F Series
Information disclosure, information tampering and authentication bypass vulnerability due to improper authentication exists in the MELSEC-F Series main modules.
[]
null
null
9.1
null
ICSA-23-331-01
Delta Electronics InfraSuite Device Master
In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists that allows an attacker to write to any file to any location of the filesystem, which could lead to remote code execution. In Delta Electronics InfraSuite Device Master v.1.0.7, a vulnerability exists that allows an unauthenticated attacker t...
[]
null
7.5
null
null
ICSA-20-147-02
Johnson Controls Kantech EntraPass
There is a vulnerability in Kantech EntraPass that could allow an authorized low-privileged user to gain full system-level privileges by replacing critical files with specifically crafted files.CVE-2020-9046 has been assigned to this vulnerability. A CVSS v3 base score of 8.8 has been calculated; the CVSS vector string...
[]
null
null
8.8
null
ICSA-22-349-11
Siemens SIPROTEC 5 Devices
A buffer overrun can be triggered in X.509 certificate verification, specifically in name constraint checking. Note that this occurs after certificate chain signature verification and requires either a CA to have signed the malicious certificate or for the application to continue certificate verification despite failur...
[]
null
7.5
null
null
ICSA-23-334-04
Mitsubishi Electric FA Engineering Software Products
Malicious code execution vulnerability due to external control of file name or path exists in multiple FA engineering software products. This vulnerability could allow an attacker to execute a malicious code by having legitimate users open a specially crafted project file, which could result in information disclosure, ...
[]
null
7.8
null
null
ICSA-22-326-03
Phoenix Contact Automation Worx
In Phoenix Contact Automation Worx Software Suite up to version 1.89, manipulated PC Worx or Config+ files could lead to a heap buffer overflow or a read access violation. Availability, integrity, or confidentiality of an application programming workstation could be compromised by attacks using these vulnerabilities.CV...
[]
null
null
7.8
null
ICSA-22-132-16
Siemens Teamcenter
The tcserver.exe binary in affected applications is vulnerable to a stack overflow condition during the parsing of user input that may lead the binary to crash. The application contains a XML External Entity Injection (XXE) vulnerability. This could allow an attacker to view files on the application server filesystem.
[]
null
5.3
null
null
ICSA-23-080-01
Keysight N6845A Geolocation Server
N6854A Geolocation Server versions 2.4.2 are vulnerable to untrusted data deserialization, which may allow a malicious actor to escalate privileges in the affected device’s default configuration and achieve remote code execution. CVE-2023-1399 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has bee...
[]
null
null
7.8
null
ICSA-20-051-03
Honeywell NOTI-FIRE-NET Web Server (NWS-3)
The Honeywell Fire Web Server 's authentication may be bypassed by a capture-replay attack from a web browser.CVE-2020-6972 has been assigned to this vulnerability. A CVSS v3 base score of 9.3 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:L/A:N). The affected product is vulnerable to a p...
[]
null
null
9.4
null
ICSA-17-222-03
Solar Controls WATTConfig M Software
An uncontrolled search path element has been identified, which could allow an attacker to execute arbitrary code on a target system using a malicious DLL file.CVE-2017-9648 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been assigned; the CVSS vector string is (AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/...
[]
null
null
7.8
null
ICSA-18-025-02B
Siemens Desigo PXC (Update C)
A remote attacker with network access to the device could potentially upload a new firmware image to the devices without prior authentication. CVE-2018-4834 has been assigned to this vulnerability. A CVSS v3 base score of 9.8 has been assigned; the CVSS vector string is (AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H).
[]
null
null
9.8
null
ICSA-23-012-03
InHand Networks InRouter
The affected products use an unsecured channel to communicate with the cloud platform by default. An unauthorized user could intercept this communication and steal sensitive information such as configuration information and MQTT credentials; this could allow MQTT command injection.-CVE-2023-22597 has been assigned to t...
[]
null
5.3
null
null
ICSA-22-256-03
Delta Electronics DIAEnergie
Executable files could be uploaded to certain directories using hard-coded bearer authorization, allowing remote code execution.
[]
null
null
9.8
null
ICSA-22-188-01
Rockwell Automation MicroLogix
The X-Frame-Options header is not configured in the HTTP response, which could allow clickjacking attacks.CVE-2022-2179 has been assigned to this vulnerability. A CVSS v3 base score of 6.5 has been calculated; the CVSS vector string is (AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:N/A:N).
[]
null
null
6.5
null
ICSA-21-040-06
ICSA-21-040-06_Siemens JT2Go and Teamcenter Visualization (Update A)
Affected applications lack proper validation of user-supplied data when parsing ASM files. This could lead to pointer dereferences of a value obtained from untrusted source. An attacker could leverage this vulnerability to execute code in the context of the current process. (ZDI-CAN-11899) Affected applications lack pr...
[]
null
7.8
null
null
ICSA-22-172-02
JTEKT TOYOPUC
The affected product lacks authentication functionality, which could allow an attacker to change controller configurations, manipulate data, or cause a denial-of-service condition.CVE-2022-29951 has been assigned to this vulnerability. A CVSS v3 base score of 7.7 has been calculated; the CVSS vector string is (AV:N/AC:...
[]
null
null
7.7
null
ICSA-23-285-04
Siemens Xpedition Layout Browser
Affected application contains a stack overflow vulnerability when parsing a PCB file. An attacker can leverage this vulnerability to execute code in the context of the current process.
[]
null
7.8
null
null
ICSA-21-257-08
Siemens Teamcenter
The "surrogate" functionality on the user profile of the application does not perform sufficient access control that could lead to an account takeover. Any profile on the application can perform this attack and access any other user assigned tasks via the "inbox/surrogate tasks". The affected application contains Insec...
[]
null
5.3
null
null
ICSA-21-194-15
ICSA-21-194-15_Siemens JT2Go and Teamcenter Visualization
The BMP_Loader.dll library in affected applications lacks proper validation of user-supplied data when parsing BMP files. A malformed input file could result in a double free of an allocated buffer that leads to a crash. An attacker could leverage this vulnerability to cause denial-of-service condition.CVE-2021-34333 h...
[]
null
null
7.8
null
ICSA-22-104-10
Siemens SICAM A8000
Affected devices do not require an user to be authenticated to access certain files. This could allow unauthenticated attackers to download these files.
[]
null
5.3
null
null
ICSA-19-344-03
Siemens RUGGEDCOM ROS (Update A)
The embedded DENX U-Boot boot loader has a locally exploitable buffer overflow via a crafted kernel image because filesystem loading is mishandled. The security vulnerability could be exploited by an attacker with local access to the affected systems. The vulnerability could allow an attacker to compromise confidentia...
[]
null
4.6
null
null
ICSA-23-047-13
Sub-IoT DASH 7 Alliance Protocol stack implementation
The Sub-IoT implementation of the DASH 7 Alliance protocol has a vulnerability that can lead to an out-of-bounds write. If the protocol has been compiled using default settings, this will only grant the attacker access to allocated but unused memory. However, if it was configured using non-default settings, there is th...
[]
null
null
5.3
null
ICSA-18-338-01
Omron CX-One
Two stack-based buffer overflow vulnerabilities have been discovered. When processing project files, the application allows input data to exceed the buffer. An attacker could use a specially crafted project file to overflow the buffer and execute code under the privileges of the application.CVE-2018-18993 has been assi...
[]
null
null
5.8
null
ICSA-19-087-01
Rockwell Automation PowerFlex 525 AC Drives
A remote, unauthenticated threat actor can repeatedly send specific CIP packets to an affected PowerFlex 525 drive, which may allow disruption of the availability of the device.CVE-2018-19282 has been assigned to this vulnerability. A CVSS v3 base score of 7.5 has been calculated; the CVSS vector string is (AV:N/AC:L/P...
[]
null
null
7.5
null
ICSA-21-280-02
Mobile Industrial Robots Vehicles and MiR Fleet Software
An authenticated local attacker with an account on the MiR robot operating system can exploit a Linux kernel vulnerability to perform privilege escalation to root or cause a denial-of-service condition.CVE-2017-7184 has been assigned to this vulnerability. A CVSS v3 base score of 7.8 has been calculated; the CVSS vecto...
[]
null
null
7.5
null
ICSA-18-088-03
Siemens SIMATIC PCS 7, SIMATIC WinCC, SIMATIC WinCC Runtime Professional, and SIMATIC NET PC Software (Update G)
Specially crafted messages sent to the RPC service of the affected products could cause a Denial-of-Service condition on the remote and local communication functionality of the affected products. A reboot of the system is required to recover the remote and local communication functionality. Please note that an attacke...
[]
null
7.5
null
null
ICSA-19-255-02
3S-Smart Software Solutions GmbH CODESYS V3 Library Manager (Update A)
The system displays active library content without checking the validity, which may allow the contents of manipulated libraries to be displayed or executed. The issue also exists for source libraries, but 3S-Smart Software Solutions GmbH strongly recommends distributing compiled libraries only.CVE-2019-13538 has been a...
[]
null
null
8.6
null
ICSA-22-132-16
Siemens Teamcenter
The tcserver.exe binary in affected applications is vulnerable to a stack overflow condition during the parsing of user input that may lead the binary to crash. The application contains a XML External Entity Injection (XXE) vulnerability. This could allow an attacker to view files on the application server filesystem.
[]
null
5.3
null
null