881f9f2 | 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255 256 257 258 259 260 261 262 263 264 265 266 267 268 269 270 271 272 273 274 275 276 277 278 279 280 281 282 283 284 285 286 287 288 289 290 291 292 293 294 295 296 297 298 299 300 301 302 303 304 305 306 307 308 309 310 311 312 313 314 315 316 317 318 319 320 321 322 323 324 325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 340 341 342 343 344 345 346 347 348 349 350 351 352 353 354 355 356 357 358 359 360 361 362 363 364 365 366 367 368 369 370 371 | """
FMSR MCP Server — Failure Mode to Sensor Relation mapping for Smart Grid transformers.
FMSR = Failure Mode Sensor Relation. Given sensor readings (especially dissolved
gas concentrations), this server helps an agent diagnose which fault type is most
likely and understand which sensors are elevated for each failure mode.
Tools exposed to the LLM agent:
list_failure_modes — catalogue of all known fault types
search_failure_modes — find fault types matching a keyword or gas name
get_sensor_correlation — which gases/sensors indicate a specific fault
get_dga_record — retrieve a transformer's most recent DGA snapshot
analyze_dga — classify a set of gas concentrations into a fault type
using the IEC 60599 Rogers Ratio method
Data source: data/processed/failure_modes.csv, dga_records.csv
"""
from __future__ import annotations
import sys
import math
from pathlib import Path
sys.path.insert(0, str(Path(__file__).resolve().parents[2]))
import pandas as pd
from mcp.server.fastmcp import FastMCP
from mcp_servers.base import load_failure_modes, load_dga_records
mcp = FastMCP("smart-grid-fmsr")
_failure_modes: pd.DataFrame | None = None
_dga_records: pd.DataFrame | None = None
def _get_failure_modes() -> pd.DataFrame:
global _failure_modes
if _failure_modes is None:
_failure_modes = load_failure_modes()
return _failure_modes
def _get_dga_records() -> pd.DataFrame:
global _dga_records
if _dga_records is None:
_dga_records = load_dga_records()
return _dga_records
# ---------------------------------------------------------------------------
# Rogers Ratio method (IEC 60599:2022 Table 1)
# ---------------------------------------------------------------------------
# A classic DGA interpretation algorithm. It computes three gas ratios and
# maps them to a fault code via a lookup table.
#
# Ratios (using the JSON's R-numbering convention):
# R1 = CH4 / H2 (IEC Table 1 middle column)
# R2 = C2H2 / C2H4 (IEC Table 1 first column)
# R3 = C2H4 / C2H6 (IEC Table 1 third column)
#
# The lookup table below follows IEC 60599:2022 Table 1 (4th edition, p.13).
# "NS" in the standard ("non-significant whatever the value") is encoded as
# (0, None) on R2 since gas ratios are non-negative.
#
# Order: most-severe first so first-match-wins resolves overlap toward the
# more severe code (e.g., D2 wins over D1 in the overlap region
# R1 ∈ [0.1, 0.5), R2 ∈ [1.0, 2.5), R3 ≥ 2.0). Boundary phrasing here mirrors
# the encoded ranges (min-inclusive, max-exclusive).
_ROGERS_TABLE = [
# (R1_range, R2_range, R3_range, code, description)
# Each range is (min_inclusive, max_exclusive); None = no bound.
((0.1, 1.0), (0.6, 2.5), (2.0, None), "D2", "Discharges of high energy (arcing)"),
((0.1, 0.5), (1.0, None), (1.0, None), "D1", "Discharges of low energy"),
((1.0, None), (0, 0.2), (4.0, None), "T3", "Thermal fault, t > 700 °C"),
((1.0, None), (0, 0.1), (1.0, 4.0), "T2", "Thermal fault, 300 °C < t < 700 °C"),
((1.0, None), (0, None), (0, 1.0), "T1", "Thermal fault, t < 300 °C"),
((0, 0.1), (0, None), (0, 0.2), "PD", "Partial discharges"),
]
def _in_range(value: float, lo, hi) -> bool:
if lo is not None and value < lo:
return False
if hi is not None and value >= hi:
return False
return True
def _ratio(numerator: float, denominator: float) -> float:
"""Compute a gas ratio with explicit zero-denominator handling.
- denominator > 0: numerator / denominator (finite)
- denominator == 0 and numerator > 0: math.inf (a real ratio that diverges)
- denominator == 0 and numerator == 0: 0.0 (genuinely no signal)
Returning math.inf for a divergent ratio is critical: collapsing it to 0.0
would silently drop samples into the wrong fault class (e.g., a sample with
nonzero CH4 and C2H4 but zero C2H6 has R3 = +inf and should match D2 if the
other ratios fit, not fall through to N).
"""
if denominator > 0:
return numerator / denominator
return math.inf if numerator > 0 else 0.0
def _ratio_field(value: float) -> tuple:
"""Normalize a ratio for JSON-safe outbound serialization.
Returns (json_safe_value, is_divergent). math.inf becomes None + True,
so `json.dumps(result, allow_nan=False)` succeeds on the public output.
Internal table matching keeps the raw float (including math.inf) — this
helper runs only at the dict-construction boundary.
"""
if math.isinf(value):
return None, True
return round(value, 4), False
def _rogers_ratio(h2: float, ch4: float, c2h2: float, c2h4: float, c2h6: float) -> dict:
"""Apply Rogers Ratio method; return IEC code and description.
Output ratio fields are JSON-safe: a divergent ratio (zero denominator,
nonzero numerator) is reported as `null` with a sibling `r{1,2,3}_divergent: true`
flag rather than `inf`. Internal table matching uses the true infinity so
classification is correct.
"""
r1 = _ratio(ch4, h2)
r2 = _ratio(c2h2, c2h4)
r3 = _ratio(c2h4, c2h6)
# All-zero gases → N. IEC 60599 Table 1 does not address the no-detectable-gas
# case explicitly; PD's R1/R3 ranges include 0 and would otherwise spuriously
# match. Operationally, no measurable gas means no fault, not partial discharge.
if h2 == 0 and ch4 == 0 and c2h2 == 0 and c2h4 == 0 and c2h6 == 0:
return {
"iec_code": "N",
"diagnosis": "Normal / Inconclusive",
"r1_ch4_h2": 0.0,
"r2_c2h2_c2h4": 0.0,
"r3_c2h4_c2h6": 0.0,
}
for r1_range, r2_range, r3_range, code, description in _ROGERS_TABLE:
if (
_in_range(r1, *r1_range)
and _in_range(r2, *r2_range)
and _in_range(r3, *r3_range)
):
return _build_result(code, description, r1, r2, r3)
return _build_result("N", "Normal / Inconclusive", r1, r2, r3)
def _build_result(code: str, description: str, r1: float, r2: float, r3: float) -> dict:
"""Build the public analyze_dga result dict with JSON-safe ratio fields."""
r1_val, r1_div = _ratio_field(r1)
r2_val, r2_div = _ratio_field(r2)
r3_val, r3_div = _ratio_field(r3)
result = {
"iec_code": code,
"diagnosis": description,
"r1_ch4_h2": r1_val,
"r2_c2h2_c2h4": r2_val,
"r3_c2h4_c2h6": r3_val,
}
if r1_div:
result["r1_divergent"] = True
if r2_div:
result["r2_divergent"] = True
if r3_div:
result["r3_divergent"] = True
return result
# ---------------------------------------------------------------------------
# Tools
# ---------------------------------------------------------------------------
@mcp.tool()
def list_failure_modes() -> list[dict]:
"""
Return the full catalogue of known transformer failure modes.
Returns:
List of dicts with keys: failure_mode_id, name, severity, iec_code,
key_gases, recommended_action.
"""
df = _get_failure_modes()
return df[
[
"failure_mode_id",
"name",
"severity",
"iec_code",
"key_gases",
"recommended_action",
]
].to_dict(orient="records")
@mcp.tool()
def search_failure_modes(query: str) -> list[dict]:
"""
Search failure modes by keyword (name, description, gas, or IEC code).
Args:
query: Free-text search string, e.g. "arc", "H2", "PD", "overheating".
Returns:
List of matching failure mode dicts (same schema as list_failure_modes).
Empty list if no matches.
"""
df = _get_failure_modes()
q = query.lower()
mask = (
df["name"].str.lower().str.contains(q, na=False)
| df["description"].str.lower().str.contains(q, na=False)
| df["key_gases"].str.lower().str.contains(q, na=False)
| df["iec_code"].str.lower().str.contains(q, na=False)
| df["dga_label"].str.lower().str.contains(q, na=False)
)
return df[mask][
[
"failure_mode_id",
"name",
"severity",
"iec_code",
"key_gases",
"recommended_action",
]
].to_dict(orient="records")
@mcp.tool()
def get_sensor_correlation(failure_mode_id: str) -> dict:
"""
Return the sensors and gases most strongly associated with a failure mode.
Args:
failure_mode_id: e.g. "FM-006" (use list_failure_modes to find IDs).
Returns:
Dict with keys: failure_mode_id, name, key_gases (list), description,
iec_code, recommended_action.
Returns an error dict if the ID is not found.
"""
df = _get_failure_modes()
row = df[df["failure_mode_id"] == failure_mode_id]
if row.empty:
return {"error": f"Failure mode '{failure_mode_id}' not found."}
r = row.iloc[0].to_dict()
r["key_gases"] = [g.strip() for g in r["key_gases"].split(",") if g.strip()]
return r
@mcp.tool()
def get_dga_record(transformer_id: str) -> dict:
"""
Retrieve the most recent dissolved gas analysis (DGA) record for a transformer.
Args:
transformer_id: Asset identifier, e.g. "T-016".
Returns:
Dict with gas concentrations (ppm) and the recorded fault label:
transformer_id, sample_date, dissolved_h2_ppm, dissolved_ch4_ppm,
dissolved_c2h2_ppm, dissolved_c2h4_ppm, dissolved_c2h6_ppm,
dissolved_co_ppm, dissolved_co2_ppm, fault_label.
Returns an error dict if not found.
"""
df = _get_dga_records()
row = (
df[df["transformer_id"] == transformer_id]
# sample_date is stored as ISO YYYY-MM-DD, so lexicographic descending order is chronological.
.sort_values("sample_date", ascending=False)
)
if row.empty:
return {"error": f"No DGA record found for '{transformer_id}'."}
record = row.iloc[0].to_dict()
return {key: (None if pd.isna(value) else value) for key, value in record.items()}
@mcp.tool()
def analyze_dga(
h2: float,
ch4: float,
c2h2: float,
c2h4: float,
c2h6: float,
transformer_id: str | None = None,
) -> dict:
"""
Classify a set of dissolved gas concentrations into a fault type using
the IEC 60599 Rogers Ratio method.
This is the core diagnostic tool: given raw gas readings (in ppm), it
returns the most likely fault classification and the three diagnostic ratios.
Args:
h2: Hydrogen concentration (ppm).
ch4: Methane concentration (ppm).
c2h2: Acetylene concentration (ppm).
c2h4: Ethylene concentration (ppm).
c2h6: Ethane concentration (ppm).
transformer_id: Optional — if provided, included in the result for
traceability.
Returns:
Dict with keys:
transformer_id (if provided), iec_code, diagnosis,
r1_ch4_h2, r2_c2h2_c2h4, r3_c2h4_c2h6,
input_gases (echo of inputs).
Ratio fields are always JSON-safe: a divergent ratio (zero
denominator with nonzero numerator) is reported as `null` plus a
sibling `r{1,2,3}_divergent: true` flag, never as a non-finite float.
Finite-ratio results omit the `*_divergent` keys entirely.
"""
# Coerce to float: LLMs sometimes pass numeric args as strings even when
# the tool schema declares "type": "number".
try:
h2, ch4, c2h2, c2h4, c2h6 = (
float(h2),
float(ch4),
float(c2h2),
float(c2h4),
float(c2h6),
)
except (TypeError, ValueError) as exc:
return {"error": f"Gas values must be numeric: {exc}"}
inputs = {
"h2_ppm": h2,
"ch4_ppm": ch4,
"c2h2_ppm": c2h2,
"c2h4_ppm": c2h4,
"c2h6_ppm": c2h6,
}
negative_inputs = {name: value for name, value in inputs.items() if value < 0}
if negative_inputs:
return {
"error": "Gas concentrations must be non-negative.",
"invalid_inputs": negative_inputs,
}
invalid_number_inputs = {
name: value for name, value in inputs.items() if not math.isfinite(value)
}
if invalid_number_inputs:
return {
"error": "Gas concentrations must be finite numbers.",
"invalid_inputs": invalid_number_inputs,
}
result = _rogers_ratio(h2, ch4, c2h2, c2h4, c2h6)
result["input_gases"] = inputs
if transformer_id:
result["transformer_id"] = transformer_id
return result
# ---------------------------------------------------------------------------